What Size Wire for a 15 Amp Circuit?

Use 14 AWG copper for a 15 amp breaker. With aluminum wire the smallest size is 12 AWG. For long runs you may need thicker wire to limit voltage drop.

The answer

14 AWG copper

12 AWG aluminum (75 °C terminals)

Wire size for a 15 amp breaker
Case Wire size Table ampacity Area
Copper · 75 °C THHN in conduit, most modern equipment 14 AWG 20 A 2.1 mm²
Copper · 60 °C NM / Romex cable, older terminals 14 AWG 15 A 2.1 mm²
Aluminum · 75 °C Needs connectors and terminals listed for aluminum 12 AWG 20 A 3.3 mm²

Calculate for your exact distance

On this page

How the answer is worked out

The breaker is 15 A. The smallest copper wire with a 75 °C table ampacity at or above 15 A is 14 AWG, rated 20 A, with a cross-section of 2.1 mm².

For 60 °C terminals or NM cable the smallest copper size is 14 AWG, rated 15 A in the 60 °C column.

Aluminum uses its own column. The smallest aluminum size at 75 °C for this rating is 12 AWG, rated 20 A. Aluminum conductors need connectors and terminals listed for aluminum.

NEC 240.4(D) also limits the breaker for small conductors: 14 AWG copper is capped at 15 A, 12 AWG copper at 20 A, 10 AWG copper at 30 A, 12 AWG aluminum at 15 A and 10 AWG aluminum at 25 A. The sizes in the table respect those caps, so a wire is never paired with a breaker larger than its limit.

Why 14 AWG and not smaller

14 AWG copper is the smallest size in this calculator, and NEC 240.4(D) caps it at a 15 amp breaker even though the ampacity table lists 20 A at 75 °C for the wire. That is why a 14 AWG wire on a 20 amp breaker is not allowed. A 15 amp breaker is the largest protection you can pair with 14 AWG copper.

When to use 12 AWG instead

Some installers run 12 AWG on a 15 amp circuit. It costs a little more but lowers voltage drop on long runs and leaves room to upgrade the breaker to 20 A later if the receptacles and loads allow it. The tables below show how far each size can go before the drop passes 3%.

Aluminum wire

Aluminum 14 AWG is not covered by the ampacity table used here. The smallest aluminum size for a 15 amp breaker is 12 AWG, and aluminum conductors must be connected with terminals and connectors rated for aluminum.

How far can you run it? (3% voltage drop)

The distance table uses the same resistance-only model as the calculator, with a 3% limit and the wire at 75 °C. Aluminum has about 1.6 times the resistance of copper for the same size, so an aluminum run of the same length drops more voltage.

Assumes the full 15 A load on a single-phase 120 V circuit, a 75 °C conductor, copper or aluminum, a 3% voltage drop limit and the one-way length in the table. Aluminum shows a dash where that size cannot carry the full current.

Maximum one-way length for 3% drop at 15 A, 120 V, 75 °C conductor
Wire size Copper Aluminum
14 AWG 38.3 ft [11.7 m] —
12 AWG 60.9 ft [18.6 m] 37.0 ft [11.3 m]
10 AWG 96.8 ft [29.5 m] 58.8 ft [17.9 m]
8 AWG 154.0 ft [46.9 m] 93.5 ft [28.5 m]

Before you buy wire

The table is a starting point. Work through this list before you order conductors, and keep the answer that matches your real installation.

This is general information based on NEC tables, not a permit or an installation plan. Local amendments, the equipment nameplate and an inspector decide what is acceptable. Read the disclaimer.