Wire Size by Amps: Breaker and Service Guides

Pick your breaker size to see the wire gauge that fits it, why copper and aluminum differ, and how far each size can run before voltage drop becomes a problem. Every answer comes from the same NEC Table 310.16 calculation engine as the wire size calculator, so the numbers match.

Guides by breaker or service size

Wire size for your situation

Pick the case that matches your circuit to see the smallest wire for that distance, load or charger.

Wire size for each breaker rating

The table lists the smallest wire for each standard breaker rating. The copper 60 °C column is the one used for NM (Romex) cable and older terminals, and the 75 °C column is the usual choice for modern equipment.

Smallest copper or aluminum wire for each breaker rating, by ampacity alone
Breaker Copper, 75 °CCopper, 60 °CAluminum, 75 °C
15 A 14 AWG14 AWG12 AWG
20 A 12 AWG12 AWG10 AWG
25 A 10 AWG10 AWG10 AWG
30 A 10 AWG10 AWG8 AWG
35 A 8 AWG8 AWG8 AWG
40 A 8 AWG8 AWG8 AWG
45 A 8 AWG6 AWG6 AWG
50 A 8 AWG6 AWG6 AWG
60 A 6 AWG4 AWG4 AWG
70 A 4 AWG4 AWG3 AWG
80 A 4 AWG3 AWG2 AWG
90 A 3 AWG2 AWG2 AWG
100 A 3 AWG — 1 AWG
110 A 2 AWG — 1/0 AWG
125 A 1 AWG — 2/0 AWG
150 A 1/0 AWG — 3/0 AWG
175 A 2/0 AWG — 4/0 AWG
200 A 3/0 AWG — 250 kcmil

Calculators

Use the Wire Size Calculator for a full answer with your run length, the Voltage Drop Calculator to check a wire you already have, or the 12V Wire Size Calculator for DC circuits.

Wire size also depends on distance and conditions; use the calculator for your exact run.